CE1N1748en
01.07.2002
Siemens Building Technologies
HVAC Products
1748
Room Temperature
Sensors
QAA24/AP
QAA25/AP
• Landis & Staefa Ni 1000 sensing element
• Units with (QAA25/AP) and without (QAA24/AP) setpoint adjuster
Use
In HVAC plants to acquire and adjust the room temperature, especially where a high
level of comfort is required.
Suitable for all systems and units that are capable of handling Landis & Staefa Ni 1000
signals, such as RWC.., RWD.., RWX62.. and RL..100.
Functions
The sensor acquires the room temperature by means of its Landis & Staefa Ni 1000
sensing element. The resistance value changes according to the ambient temperature.
Type summary
Type reference Description
QAA24/AP Room temperature sensor
QAA25/AP Room temperature sensor with setpoint adjuster from 5 to 35 °C
ARG70 Adapter plate 120 x 120 mm for 4 x 4 conduit boxes
ARG70.1 Adapter plate 96 x 120 mm for 2 x 4 conduit boxes
Mechanical design
The units have been designed for wall mounting. They are suitable for use with most
commercially available recessed conduit boxes. The cables can be introduced from the
rear (concealed wiring).
2/4
Siemens Building Technologies QAA24/AP and QAA25/AP Room Temperature Sensors CE1N1748en
HVAC Products 01.07.2002
Installation notes
On a flat inner wall of the space to be heated or air conditioned. Not in recesses,
shelves, not behind curtains, not opposite or near heat sources. The unit must not be
exposed to direct solar radiation.
• When installing the unit, fix the baseplate first, then hook on the body and make the
electrical connections. Then fit the cover and secure it.
• The end of the conduit at the sensor must be sealed to prevent false measurements
due to draughts through the conduit.
• The permissible environmental conditions should be observed.
• Installation instructions are printed on the packing.
•
Technical data
Operating range 0 ...50 °C
Setting rang for QAA25/AP 5...35 °C
Temperature setpoint: 5 °C
35 °C
corresponding resistance: 100 Ω
660 Ω
Sensing element Landis & Staefa Ni 1000 (1000 Ω at 0 °C)
Maximum voltage AC 24 V
Time constant (with air movement)
QAA24/AP
QAA25/AP
approx. 7 min
approx. 7 min
Terminals for cross-sectional areas of 2 x 1.5 mm2 or 1 x 2.5 mm2
Operation
Climatic conditions
Temperature
Humidity
Pollution degree
to IEC 721-3-3
class 3K5
0...50 °C
<85 % r. h.
normal, to EN 60730
Transport
Climatic conditions
Temperature
Humidity
to IEC 721-3-2
class 2K3
-25...+65 °C
<95 % r. h.
Mechanical conditions class 2M2
Safety class III to EN 60 730
Degree of protection IP 30 to EN 60 529
CE conformity to EMC directive 89/336/EEC
Weight approx. 0.1 kg
Colour white, NCS S 0502-G (RAL 9003)
Internal diagram
L&S
Ni 1000
B1M 174
8G
01
QAA24/AP
B2 B1M
L&S
Ni 1000
17
48
G
02
QAA25/AP
B1 Room temperature signal
B2 Setpoint signal
M Measuring neutral
Location
Notes
General unit data
Connection
Environmental conditions
Requirements
Miscellaneous
3/4
Siemens Building Technologies Template PrDbA4b.dot zu Produkt-Datenblatt CE1N1748en
HVAC Products 01.07.2002
Knob slots with temperature position
Dimensions
96,4
99
,6
42,8
30
02
M
01
28
28
30
01
M
02
30 30
28
3,6
30
30
28
86
86Unit and Baseplate
4/4
Siemens Building Technologies QAA24/AP and QAA25/AP Room Temperature Sensors CE1N1748en
HVAC Products 01.07.2002
2002 Siemens Building Technologies Ltd.