AIRBUS INDUSTRIE
AIRBUS
TECHNICAL
DIGEST
NUMBER 21
MAY1997
FAST / NUMBER 212
A330/A340
CARGO BAY CONDENSATION
AND SMOKE WARNINGS
Solutions available
In the last issue of the FAST magazine the
carriage of perishables and livestock
was discussed. In this article a more
specific challenge to the cargo
smoke detection system,
caused by excessive
humidity, is examined.
Pneumatic, Fire and Ice Protection Engineers,
Engineering and Technical Support, Airbus Industrie, Customer Services Directorate
Claire Nurcombe
By
and Mike Carver
TheAirbus Air Cargo market forecast indi-cates that transportation
of cargo is the fastest growing area of
aviation, with the world’s freighter
fleet growing at an annual average of
6.7% until 2015. A large amount of the
cargo carried will be moisture and heat
carrying, e.g., animals, fruit and veg-
etables. This moisture and heat has the
potential to be released over the period
of time that the cargo remains in the
hold. Operations in hot and humid en-
vironmental conditions can also lead to
occurrences of the same phenomenon.
With the opening of the cargo doors
there is an influx of hot and humid air.
This affects the environmental condi-
tions within the hold in the same way
as the presence of heat and moisture
producing cargo. False smoke alarms
may occur in both circumstances due
to interference of condensation with
the smoke detection system.
The condensation formation may be
affected by the ventilation and heating
options for the cargo hold taken by the
operator. There are several options for
ventilating and heating the cargo bays.
In the forward cargo bay there is a ba-
sic option for ventilation, and tempera-
ture control and/or ground ventilation
can also be installed. In the aft com-
partment ventilation is a basic option
and in the bulk cargo bay ventilation is
fitted on all aircraft. In the bulk cargo
bay heating and/or ground ventilation
can also be installed.
The ventilation systems for the for-
ward, aft and bulk cargo compartments
all have the same architecture. Two
fans are fitted, one to draw air into the
compartment and one to draw out air.
The expelled air is ducted towards the
outflow valve, which ensures that most
of the air is not recirculated. Since this
is only operative in flight there is an
extra option to enable ventilation on
the ground.
The option for heating the bulk cargo
bay consists of an heating element
heating the incoming air. There is no
true regulation of the system; it is only
possible to heat the bulk cargo com-
partment, and there is no facility for
cooling the compartment. This system
differs from the forward cargo bay sys-
tem, which allows true temperature
control, with heating and cooling of the
compartment.
Both heating and ventilation should
ensure that in-flight spurious smoke
warnings due to condensation are pre-
vented (since the detectors will be
warmed by the heated circulating air
and the ventilation will help reduce the
amount of water vapour in the air).
However, in cases of the carriage of
extreme humidity producing cargo, in-
flight spurious warnings due to con-
densation may still occur. Also, with
the cargo hold at a nominal tempera-
ture of 20°C, condensation formation
is still possible if the cargo doors are
opened in very hot and humid condi-
tions, where 20°C may be below the
dewpoint temperature of the outside
air.
Condensation forms because the de-
tectors are cooler than the air entering
the cargo hold, either because of venti-
lation in the hold, or because of the
cold soak during a long flight. When
the hot and humid air enters the cargo
bay a disparity occurs between the rel-
ative humidity within the hold and the
temperature of the detectors. This may
lead to the situation where the dew-
point temperature of the humid air is
above the temperature of the detectors.
In these conditions condensation can
form on the grid in the measuring
chamber of the smoke detector. The
condensation causes a change in the
current in the measuring chamber,
which is the criteria for giving a smoke
alarm. These false alarms occur on
long range aircraft of all types, this for-
mation of condensation being exacer-
bated by the length of time a long haul
aircraft may be airborne.
Over the duration of the flight, if no
cargo ventilation is present, the humid-
ity level in the cargo bays will increase
while the temperature of the smoke de-
tectors drops. This provides the perfect
conditions for condensation to form.
A solution has been developed by
Airbus Industrie to prevent spurious
alarms due to condensation occurring
on the A330 and A340 aircraft.
FAST / NUMBER 21 3
CARGO COMPARTMENT A330-300 A340-200
MODIFICATION OPTIONS /A340-300
Forward Ventilation (basic option) Mod 40096 Mod 40186
compartment Temperature control Mod 40097 Mod 40188
Ground ventilation Mod 40220 Mod 40220
Aft Ventilation (basic option) Mod 40098 Mod 40190
compartment
Bulk Ventilation
cargo Compartment heating Mod 40099
compartment Ground ventilation Mod 40221
Cargo compartment smoke
detector hood
Forward
cargo
compt.
Aft
cargo
compt.
Smoke
Smoke
Avionics
Smoke
FAST / NUMBER 21
SYSTEM OPERATION
The lower deck cargo compartment
(LDCC) smoke detectors on the A330s
and A340s are installed in pairs. Each
pair of detectors is supplied with
power by a dual redundant power sup-
ply (see Figure 1). One detector in the
pair is installed on the Smoke
Detection Control Unit (SDCU) loop
A, the other on loop B. To trigger an
alarm a signal from each detector in
the pair is needed. However, if one
loop is not functioning, a signal from
only one detector is able to trigger an
alarm. The SDCU tests each loop to
check whether it is functioning before
it acts on a smoke alarm from a single
smoke detector. When a smoke alarm
is generated by the SDCU the ventila-
tion and heating systems (if installed)
will be closed automatically.
The detectors used on Airbus aircraft
are of the ionisation type that detect
both visible and invisible fire aerosols
(particle diameter between 0.01m to
10 m m). The ionisation detector utilises
the phenomenon that air ions are at-
tracted by smoke particles. The elec-
trodes set up an electric field and the
air between the electrodes is ionised
(made electrically conductive) by a
weak radioactive source (refer to
Figures 2 and 3 for schematic diagrams
of the smoke detector operation).
These ions move under the influence
of the electric field, setting up an ionic
current. Smoke particles are too large
(up to 1000 times larger than the ions)
to be ionised and also attract the ions
present between the electrodes. These
resulting heavy ions are virtually im-
mobile, reducing the ionic current,
which as a consequence increases the
electrical resistance of the measuring
chamber. An imbalance is now present
between the measuring chamber and a
reference chamber. This imbalance in
voltage is amplified and compared to
four different threshold levels:
l The smoke threshold. The voltage at
which the detector recognises that
smoke is present in the measuring
chamber and gives an alarm signal.
l The prefault high threshold. The
voltage at which the detector senses a
rise above the normal operational volt-
age range.
l The prefault low threshold. The volt-
age at which the detector senses a fall
below the normal operational voltage
range.
l The fault threshold. The voltage at
which the detector gives a fault signal.
The reference chamber in the detec-
tor is present to allow for differential
pressure and temperature changes en-
suring that the detectors operate with
the same sensitivity in flight and on the
ground.
Battery BUS
28VDC
Channel 1
Loop A
Channel 1
Loop B
Channel 2
Loop B
Smoke
test
LDCC
smoke lamps
Avionics compartment
smoke lamp
Avionics
compt.
smoke
detector
Lavatory
smoke
detectors
Lavatory
smoke
detectors
Crew rest
smoke
detection
control unit
Stairwell
smoke
detector
Avionics
compt.
smoke
detector
LDCC
smoke
detectors
1WH
3WH
5WH
7WH
9WH
LDCC
smoke
detectors
2WH
4WH
6WH
7WH
10WH
Power
channel 1
Power
channel 2
Normal BUS
28VDC
SDCU
Smoke
Detection
Control
Unit
4
Figure 1
Smoke detection loop schematic for A340
INVESTIGATION
The investigations into the spurious
smoke alarms due to condensation
were mainly concentrated with two op-
erators, one operating in the Middle
East and one in the Far East.
Questionnaires were also sent to other
A330/A340 operators susceptible to
spurious warnings to discover how
widespread the spurious alarms were.
Some common factors high-lighted in
the replies to the questionnaire allowed
Airbus Industrie to suggest some short
term solutions to help reduce delays
and inconvenience. An effective short
term solution was drying the smoke
detectors with a hot air source, but this
was a maintenance burden and not
practical for the operators in the long
term. It was also suggested that the
cabin should be heated to the maxi-
mum temperature (28°C) if no passen-
gers were present on the flight, to have
the cargo ventilation, if installed, on at
all times and to heat the bulk cargo
hold, if possible.
In January 1995 testing took place
on an A340 to define the environment
and to determine the effect of localised
heaters on the smoke detectors. One of
each pair of detectors was instru-
mented to measure temperature, hu-
midity, sensitivity and smoke indica-
tion. The cabin temperature, aircraft
skin temperature and the ambient con-
ditions on the ground were also
recorded for each flight.
In total five flights were made, the
first between Hong Kong and Osaka
and the other four between Singapore
and Hong Kong. The last two flights
made were with heaters fitted in smoke
detectors 1WH and 7WH (the two de-
tectors seen as being most susceptible
to the formation of condensation, see
Figure 4 on the following page). This
susceptibility to condensation when the
cargo doors are opened was shown by
information previously taken during
the investigation. This susceptibility is
probably due to proximity to the door.
The conditions on the ground (tem-
perature approximately 25°C, relative
humidity 50-100% throughout the test
period) did not lead to any false
alarms, but enough data was collected
from flights 2 and 3 to be able to con-
clude that there was a direct, although
small, influence of hot and humid con-
ditions on the smoke detector sensitiv-
ity signal.
On flight 2 the sensitivity dropped.
The signal moved from -4.6V to -4.9V
on 1WH (the detector was not heated
on this flight, -4.5V being the normal
signal and -6.0V a smoke alarm), while
on flight 3 the sensitivity dropped, the
signal changing from -4.9V to -5.2V
on 3WH (an unheated detector).
The lowest sensitivity signal was
shown after the cargo doors had been
shut. Installing a heater to the smoke
detectors did not have any detrimental
effect on the smoke detector sensitivity
signal.
FAST / NUMBER 21
Figure 3
Cargo smoke detector - Description of operation during smoke conditions
Figure 2
Simple schematic of cargo smoke detection operation
Electrode
Ionisation
sources
IonsFire aerosols
During smoke conditions the ion flow in the measuring chamber is impeded
with relation to the reference chamber. This creates an imbalance between
the two chambers and a smoke alarm is generated.
Reference chamber
Measuring
chamber
Ionisation source
Reference chamber shell
Fire aerosols
Ionisation source
5
Airbus currently uses the ionisation type of smoke detectors but is also undertaking a review into the latest technology
optical smoke detectors. The Scattered Light Detector is the optical smoke detector which is most suited for the use in
cargo holds. The photodiodes used in these detectors are semiconductor devices for detecting and measuring radiant
energy (as light) by means of its conversion into an electric current.
The photodiodes and LEDs are arranged so that light from the LEDs does not fall on the photodiodes under normal
conditions. The optical properties of some types of fire aerosol lead to a scattering of the emitted light, some of which will
fall on to the photodiodes.
This increase in the amount of light detected by the photodiodes causes a change in the electric current output by the
photodiode.
FAST / NUMBER 216
EVALUATION
Following the results of the flight test-
ing, it was decided to proceed with a
heated smoke detector design, rather
than a change to the grille design or
adding a curtain to the cargo bay doors.
Heating the smoke detector raises
both the temperature of the detector it-
self and the air inside the detector.
Both of these help to reduce the rela-
tive humidity within the measuring
chamber.
Heating the detector also raises the
detector temperature higher than the
dewpoint temperature of the ambient
ground conditions (or the dewpoint of
the cargo). These factors reduce the
likelihood of condensation forming. It
was decided that the optimum way of
heating the detector would be to heat
the cell cover inside the protective
cover, which would ensure a minimum
temperature differential between the
reference and the measurement cham-
bers. It was decided to regulate the
temperature of the smoke detector to
15 degrees over the ambient conditions
(to a maximum of 40°C) to optimise
the detection ability. Each pair of de-
tectors has a dual redundant heater
power loop and as before, the SDCU
would check and verify smoke alarms
from just one detector.
An Electromagnetic Inductance filter
was also required for the smoke detec-
tor. Fluctuations in the 28V electrical
bus can occur during switches between
Forward
cargo
compartment
3WH
4WH
FWD
1WH
2WH
Aft
cargo
compartment
Bulk
cargo
compartment
FWD
5WH
6WH
7WH
8WH
9WH
10WH
AIRBUS INDUSTRIE IS CURRENTLY EXAMINING NEW ADVANCES IN OPTICAL SMOKE DETECTOR
TECHNOLOGY
Figure 4
Position of smoke detectors within the cargo bays
power sources (ground power, APU
and engines). These fluctuations could
cause the heater coil to act as a sole-
noid, producing a magnetic effect that
could either cause a loss of smoke indi-
cation capability or false smoke
alarms. The electronic filter prevents
such adverse side effects.
The evaluation units were tested for
six months in operational conditions.
At the end of the evaluation period it
was judged that the heater coil was
successful in preventing spurious
smoke alarms. During the six months
no spurious warnings had occurred,
against what could normally be ex-
pected (between three or four spurious
smoke warnings per month to three or
four per week, depending on the opera-
tor and the environmental conditions).
FAST / NUMBER 21 7
• Mod 43967 - Wiring
• Mod 44177 - Heated smoke detectors
Available through the A330/A340 LRIP (Long Range Improvement Programme)
• SB 26-3009 (A330) and SB 26-4011 (A340) - Wiring for heater and EMI filter box
Issue date: Rev. 2, 30.09.9
• SB 26-3014 (A330) and SB 26-4015 (A340) - Fitting of heated smoke detector
Issue date: 04.06.96
Two Service Information Letters have also been issued concerning false smoke alarms.
These give advice about the environmental and operational conditions that could give rise to false warnings.
• SIL 26-003 (A300)
• SIL 26-022 (all aircraft types)
Heated smoke detector P/N 4370-264
THE SERVICE BULLETINS AND MODIFICATIONS THAT ARE AVAILABLE ARE SHOWN BELOW:
CONCLUSION
Retrofitting the modifications on in-service aircraft started at the beginning of 1996.
The cargo smoke detectors are an essential component of the fire protection system, but are susceptible to false alarms if
the conditions in the hold are hot and humid. Long range aircraft of all types suffer from this phenomenon, but Airbus has
solved the occurrence of false alarms by introducing heated smoke detectors.
There were two main requirements for a new detector:
l The relative humidity within the smoke detector measuring chamber had to be reduced without compromising the detec-
tors’ effectiveness.
l The dewpoint temperature of the detector had to be raised above the dewpoint temperature within the cargo bay.
Both of these requirements could be solved by heating the smoke detector to a nominal temperature above ambient condi-
tions.
The new detector included a heater coil that was capable of causing electromagnetic interference. A filter was therefore
added to the design to protect the detector from the effects of electromagnetic induction.
Six months of testing took place to ensure that the heated smoke detectors would enter service without the need for further
modification.
The main uptake of the modification by operators has been in the Far and Middle East, since many European operators
have not experienced problems with the cargo fire detection system. This is due to the less extreme environmental conditions
encountered in Europe and as the man-hours required for the wiring modification are fairly substantial it is not seen as eco-
nomical to perform this modification.
Airbus has successfully solved the occurrence of spurious alarms due to condensation on its long range aircraft. There have
been no reported smoke alarms due to condensation from operators who have the heated smoke detectors fitted to their A330
and A340 aircraft. n
FAST / NUMBER 218
by Frédérique Rigal
A330/A340 Maintenance Systems Engineer
Engineering and Technical Support
Airbus Industrie
Customer Services Directorate
The concept of on-board
centralised maintenance was
developed with the A320. The aim
was to provide maintenance teams
with diagnosis of faults in plain
English, through a single location
in the cockpit, with homogeneous
access to the maintenance
information related to the various
electronic systems. As a highly
interactive tool, the Centralised
Fault Display System (CFDS) has
evolved with in-service experience,
which has also benefited the
A330/A340 Central Maintenance
System (CMS) (described in
FAST 16, April 1994) in terms of
homogeneity of interfaces and
definition of layout, reports
and messages.
CENTRALCENTRAL
MAINTENANCEMAINTENANCE
SYSTEMSYSTEM
OPTIONOPTION
PPAACKCKAAGEGE
A330/A340
Simplifying maintenance
9
TheCMS in the A330/A340family is based on thesame core principles and
basic functions as in the A320 family :
l fault monitoring and diagnosis is
undertaken by the Built In Test
Equipment (BITE) of each system;
l a dedicated computer, Centralised
Fault Display Interface Unit (CFDIU)
on A320 and Central Maintenance
Computer (CMC) on A330/A340, con-
centrates the messages sent by the
BITEs, edits maintenance reports and
provides an interface to the operator
with the maintenance part of the con-
nected systems;
l a Post Flight Report is generated after
each flight; it lists the ECAM warnings
and maintenance status triggered during
the last flight, as well as the corre-
sponding fault messages produced by
the BITEs;
l test capabilities and access to addi-
tional systems maintenance information
are provided through the System
Report/Test function.
In addition to these basic functions,
Airbus Industrie, in cooperation with
the A330/A340 operators, has devel-
oped a batch of new features to enlarge
the capabilities of the Central
Maintenance System - The A330/A340
CMS Option Package (Figure 1). This
package can be divided into three cate-
gories :
l features improving the Trouble
Shooting process by providing addi-
tional information such as flags and ad-
visories on the Post Flight Report
(PFR) and new means of transmission:
information downloading on to a disk,
and sending BITE reports following up-
link requests from the ground;
l the Servicing Report gathers a num-
ber of parameters, such as oil/liquid
levels, status of filters, pressures, etc.,
with the aim of reducing the servicing
workload;
l the Configuration Management
Reports allow the airline to know which
part numbers, serial numbers and data-
bases are fitted on their aircraft; every
configuration change is also detected,
memorised and transmitted in real t