New hybrid circuit breaker/current limiter with serial and
parallel commutation assistance
Brevet n° 03 293 050.5
Ronan BESREST - CAPSIM
Pierre SELLIER - TECHNICATOME groupe AREVA
Claudio ZIMMERMAN - EPFL
Abstract - This paper presents a new hybrid
circuit breaker topology based on the use of
serial and parallel semiconductors that
allows to increase the supply voltage and
default current with no arc, and to benefit
from a current limitation function.
A concrete marine application, with 6.6 kV AC
breakers, have been studied and simulated
for the DGA (French defence procurement
agency). The whole constraints have been
shared between the different components in
order to optimise the system. This new circuit
breaker shows interesting performances and
new functionalities that should be able to
give additional margins on network
components design.
INTRODUCTION
Medium voltage circuit breakers are classically
electromechanical device. In such systems, the
circuit breaking is realized with the extinction of
an electrical arc when the breaker opens.
The latest progresses in power electronics make
realistic to replace the mechanical part of a
circuit breaker by semiconductors, in order to get
fast and long life systems. Such static circuit
breakers have been tested but one major
disadvantage is the thermal losses due to the
voltage drops.
Hybrid breakers based on a fast mechanical
switch and semiconductors connected in parallel
are also studied in order to get all the
advantages of semiconductors and avoid
disadvantages of conduction losses.
Fig 1: basic hybrid AC breaker topology
When the mechanical switch opens, a small arc
voltage deflects the current in the
semiconductors branch which finally interrupts
the fault current. IGCT (integrated gate turn off
thyristor) have been used successfully in such
medium voltage applications [1].
But limitation in off state blocking voltage and
current level are always problematic with static
components especially in our focused application
(6.6 kV).
The presented solution based on serial IGCT
cells and parallel thyristor commutation
assistance modules allows the use of hybrid
solutions in new fields of application. Thanks to
these modules it is possible to reach greater
power and voltage levels in power breaking
applications.
APPLICATION CONTEXT
This study was realised on the requirement of
the DGA (Délégation Générale pour l’Armement
– (French defence procurement agency) in the
context of the All Electric Ship Program. The final
aim of this circuit breaker is to be integrated in a
three phases 6.6 kV/60 Hz marine power plant.
Fig 2: application network topology
Its main function is to protect a 6.6kV/440V
transformer with a rated load from 1.5 MW to
IGCT
6.6 kV / 60 Hz
440 V / 60 Hz
1,5/5 MW
Circuit
breaker
5MW. The power sources on the network are
turbo generators and diesel generators that work
in parallel operation.
A - Main specification of the hybrid breaker
• The arc energy should be minimal or null in
order to get a long life breaker with minimal
maintenance.
• In fault conditions, the breaker should be
able to eliminate the default after a time
switch delay in order to manage time
selectivity for protection plan.
• Thermal losses on the breaker should be
minimized because in this embarked
network, cooling systems must be light and
reliable (natural convection).
• The mechanical part should be basic
because of a harsh mechanical environment.
B - Voltage constraint
The rated voltage is 6.6 kV, but normal voltage
variations in this isolated network should be
considered (+-16%). Special conditions of non
synchronous coupling of the three phases have
to be taken into account. As a result, the global
voltage constraint is: Uppmax = 12.5 kV.
C - Current constraint
The protected load is from 1.5 to 5 MW. The
current constraints are:
The maximal current rising speed is 20 kA/ms
and occurs on a medium short circuits case.
If we consider the classical hybrid AC breaker
topology (fig 1) and the actual available
semiconductors properties, the number of
needed serial IGCT is 4 in this application. They
are necessary to withstand a turn off voltage of
12.5 kV with safety margins. The arc voltage
used to deflect the current [1] should be greater
than 16 V and should be reached in a short time
in order to minimize the arc energy.
Considering these values, increasing the
application voltage to 6.6 kV leads to a
significantly fast mechanical switch. The needed
speed and voltage to withstand in our context for
a non energetic arc cannot be reached easily
with actual mechanical switch basic
technologies.
PRESENTATION OF THE SOLUTION
A new topology is proposed in order to manage
the voltage and current constraint. The main idea
is to share the voltage constraint between the
fast mechanical switch and a serial
semiconductors cell. The aim is to get no arc
using a basic fast mechanical switch and
allowing minimal conduction thermal losses. This
topology is build following a modular and
functional approach.
A- Circuit breaker modules
The different functional subsets of this new
hybrid circuit breaker are shown below:
Fig 3: novel breaker topology
Module 1: Main conduction module
It has to conduct the current with no losses. After
the break, it has to withstand the complete
supply voltage of 6.6 kV. This module is based
on a fast mechanical contact.
Module 2a: Deflection serial assistance
This block is designed in order to increase the
voltage in the main branch and to enable the
current deflection in the parallel branch.
This module is composed with two IGCT cells
put in an anti-parallel position. These cells are
modern versions of the GTO cells. It is the best
device today for this application because it is
able to conduct high currents (>4000A) with
about 1V voltage drop, and to block a high off
state voltage (4500V).
In parallel of these IGCT cells, a Metal Oxyde
Variator (MOV) has been added. The threshold
voltage of the MOV is lower (2.8 kV) than the
supply voltage value. When the semiconductors
are turned off, the MOV provides a voltage, and
the current begins to deflect in the parallel
branch. With this module, it is not necessary to
No load 0.7 A
1.5 MW rated load 150 A
5 MW rated load 500 A
Low voltage short circuit 2340 A
Medium voltage short circuit 100 kA
4 Energy storage
and discharge
2b Parallel
deflection arc
limitation
Main conduction
module
3 Current limitation
2a Deflection
serial assistance
Lc
C R1
Thyristors
MOV
IGCT
S
La
use an arc voltage to deflect the current any
more.
Module 2b: Parallel deflection and arc
limitation
Module 2a deflects the current in the parallel
branch through the module 2B path. This module
conducts the current and enables module 1 to
turn off without any electrical arc (when the
current is null). It is composed with to 2 anti-
parallel cells of 3 serial 8.2kV thyristors. These
thyristors are finally used to cut the current.
Module 3: Current limitation module
This module is used to limit the current and cut it
after it has passed by cell 2b. It is composed with
inductive impedances. These inductances are
needed to protect the circuit breaker during the
short circuit current circulation in the parallel
branch, especially if a time switch delay is
needed.
Module 4: Energy storage and discharge
The short circuit current inductive energy is
stored in the capacitor module, before being
discharged in the parallel resistor. The chosen
capacitor can be film metallized capacitors for
pulse discharges. These capacitors have a very
high energy density (up to 1kJ/L). Unfortunately,
these capacitors are unidirectional in voltage.
Consequently, a Graetz bridge is used to
maintain a positive voltage on the capacitor.
B- Circuit breaker basic working sequence
When the circuit breaker is on, the current goes
through the main conducting module 1, as the
IGCT are on.
When a fault occurs, the IGCTs are turned off,
and a voltage of 2.8 kV appears in the main
branch between the MOV terminals. The parallel
branch thyristor is then positively biased and
turned on, so the current is deflected from the
main path to the parallel path. Then the
mechanical switch opens with no current, so
without arc.
The capacitor C is used to store the inductive
energy of the electrical network. The global line
inductances associated with the capacitor
represent an oscillator circuit. This oscillator
circuit creates a current pulsation that allows to
get a fast null current and to turn off the
thyristors.
After the break, the capacitor discharges down
through the resistor.
Two variant topologies are possible:
- Without auxiliary inductance La - for an
immediate switch of breaker
In this circuit, the current is cut off after half a
sine wave period at a high frequency pulsation in
a short time and under limited curent.
- With auxiliary inductance La - for a switch
time delay breaker with current limitation
With this variant circuit, an auxiliary inductance is
settled between the thrystors cell and the final
breaker therminals. The idea is to be able to
maintain a default current in the parrallel branch
during several sine wave period without
overpassing the capacitor voltage limit. This is
possible if the current is limited by a sufficient
impedance, the auxiliary inductance (La).
RESULTS
These results are based on numerical
simulations and analytical calculations on a
complete circuit. The variable network
inductance has been choosen as a worst case
(Ld=280uH). The real components are choosen
in manufacturer catalogs after a complete
design.
The following switch off sequences are based on
a medium voltage short circuit stess simulated
on the 6.6kV transformer terminals (fig 1).
A – Circuit breaker without auxiliary
inductance
Switch off sequence:
Fig 4: switch off without auxiliary inductance La
Capacitor voltage (V)
Mechanical switch voltage (V)
Current in the network (A)
Current in the switch (A)
When the short circuit measured current reaches
1500A, an order is sent to the mechanical switch
for its opening. It takes almost 100µs before the
effective opening (mechanical delay). The IGCT
cell is turned off during this delay but not too
early in order to limit the rising voltage on the
capacitor.
Then, the current in the main branch, goes
through the MOV, which saturates and applies a
voltage on the thyristors branch.
This voltage enables the proper thyristor to be
turned on. The current is then deflected in the
parallel branch, and the mechanical switch
opens while the current in the main branch is
null. The Lc inductance limits the rising current in
the thyristor in order to protect it at turn on.
The current is null, after half a period of the
resonant circuit. In our particular case, it takes
600us. When the current is null in the thyristors
cell, these ones are turned off. The maximum
current value is lower than 3800A.
Switch on sequence
The MOV of the module 2a turns on when its
voltage is greater than a threshold Uvo. This
threshold is lower than the supply voltage
Consequently, the mechanical contact has to be
switched on when the supply voltage is lower
than Uvo, in order that no current will go through
the contact while it closes, and no arc will be
produced. So this circuit breaker can switch the
power on during a time period tuv each half a
period of the sine wave as it is shown on the
picture below:
Fig 5: switch on without auxiliary inductance
B - Circuit breaker with auxiliary inductance
Switch off sequence:
Fig 6: switch off with auxiliary inductance
With the help of the auxiliary inductance, the rise
in current is bounded and the time before
switching off the thyristors can be longer. Indeed,
the voltage of the capacitor does not reach the
same value than in the former case.
As the auxiliary inductance is high (>1.5mH), the
LC oscillating frequency is lower and the current
crosses zero after a complete supply voltage
period. The limited default current can be
maintained in the parallel branch for several
periods. Thus it can be tuned by a variation of
the delay angle of the thyristor switches.
The first interest is the possible time switch delay
in the breaker turn off that allows using time
selectivity in the network protection plan. The
second advantage is to be able to limit the
default current to about 10 kA a 60 Hz the
parallel branch instead of 100 kA that was the
normal short circuit current value
Switch on sequence:
The limitation current function cell enables a soft
switch on. Indeed, it is possible to activate the
parallel branch first with a tuneable current level
by the use of variable delay angle of the thyristor
switches. This function can be used to manage
the magnetisation of the transformer load, with a
proper decreasing of the angle. When the
minimum angle is reached, the voltage of the
circuit breaker is null, and the mechanical
contact can be closed
+UV0
tUV
Closing of the mechanical switch
-UV0
Capacitor voltage (V)
Mechanical switch voltage (V)
Current in the network (A)
Current in the switch (A)
C - Additional calculations
The calculation of the thermal losses shows that
in rated conditions, they does not overpass
191W that enables the use of natural convection
to evacuate the themal power.
COMPARISON WITH EXISTING SYSTEMS
A – Comparing with electromechanical
solutions
• The turn off time delay can be managed from
600us to several milliseconds according to
the protection plan.
• The short circuit current value can be
managed.
• The interruption is realized with no arc so the
mechanical breaker is not damaged at each
sequence.
• The phenomena are easier to manage and
more reproducible compared to the
phenomena in a breaker chamber.
• Modular functional concept which allows
optimisation according to network
architecture and application.
• New functions can be added on the same
equipment:
– Default current limitation.
– Transient current limitation (soft turn
on, motor start...).
These functions can deliver margins in the
design of other network components.
B – Comparing to hybrid/static solutions
• The supply voltage is increased to 6.6kV with
a basic fast mechanical switch.
• The short circuit power can be higher (the
initial peak current default value can reach
100 kA). With static topologies, it would lead
to a huge number of serial semiconductors to
withstand such a current
• The thermal losses are reduces compared to
static solution that allows natural convection.
• It is possible to get a time switch delay for
the breaker detection logic.
• Current limitation functions are available.
FUTURE DEVELOPPMENTS
This new topology concept for medium circuit AC
breakers has been tested successfully in
simulation. It should be validated on real
conditions. The next step in this study, which is
beginning at the present time, is to develop a
reduced scale prototype in order to demonstrate
for each module that the constraints are
withstood in every severe condition.
CONCLUSIONS
This new hybrid circuit breaker is a modular
concept that can be used to manage severe
electrical constraint on a medium voltage
embarked network. It should be able to interrupt
fault current with no arc. The voltage and current
constraints can be shared between the
components in order to fulfil the requirements.
The use of serial IGCT with minimal thermal
losses allows decreasing the complexity and
speed of the mechanical part of the system.
New functions of current limitation are available
by the use of a variant topology that integrates
an auxiliary inductance. Such functions could be
able to give new margins in the equipment
definition of the networks.
Numerical simulation gave impressive results
concerning interruption time and current
limitation capability. This topology will be soon
tested on a prototype that is developed at
present time.
[1] Jean-Marc Meyer - Etude et réalisation d’un
disjoncteur hybride ultra rapide à base de
thyristor IGCT- Thesis EPFL 2000.
[2] Jungblut - Hybrider Schnellschalter mit
Dioden als Kurzzeitladungsspeicher
VDI Reihe 21 Nr. 269 Düsseldorf: VDI Verlag
1999.
[3] Holaus - Ultra fast switches – Basic elements
for future medium voltage switchgear -Thesis
ETHZ No. 14375 dem Walter Holaus, 2001.
[4] Steurer - Ein hybrides Schaltsystem für
Mittelspannung zur strombegrenzenden
Kurzschlussunterbrechung. Thesis ETHZ 2001.
M. Steurer.
Abstract
INTRODUCTION
APPLICATION CONTEXT
A - Main specification of the hybrid breaker
B - Voltage constraint
C - Current constraint
PRESENTATION OF THE SOLUTION
A- Circuit breaker modules
Module 1: Main conduction module
Module 2a: Deflection serial assistance
Module 2b: Parallel deflection and arc limitation
Module 3: Current limitation module
Module 4: Energy storage and discharge
B- Circuit breaker basic working sequence
RESULTS
A – Circuit breaker without auxiliary inductance
B - Circuit breaker with auxiliary inductance
C - Additional calculations
COMPARISON WITH EXISTING SYSTEMS
A – Comparing with electromechanical solutions
B – Comparing to hybrid/static solutions
FUTURE DEVELOPPMENTS
CONCLUSIONS
Menue