Product Data Sheet
00813-0100-4028, Rev CA
March 2008 Rosemount 285 Annubar Primary Element
• Des
• Incr
ma
• Ene
per
• Ind
cre
(AP
Ros
Rosemount 285 Annubar®
Pri
Contents
The 285 Annubar Primary Element Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
285 Annubar Primary Element Series Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Rosemount 285 Annubar Primary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6
Configuration Data Sheet (CDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
Fluid Data Sheet (FDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15
www.ro
igned for general purpose applications
eased plant uptime with the
intenance-free design
rgy savings gained through minimal
manent pressure loss
ustry leading integrated DP flowmeters are
ated when Annubar Averaging Pitot Tube
T) primary elements are packaged with
emount pressure transmitters
mary Element Series
semount.com
Product Data Sheet
00813-0100-4028, Rev CA
March 2008Rosemount 285 Annubar Primary Element
The 285 Annubar Primary Element Series
Designed for general purpose applications
The Annubar’s revolutionary shape with sensing holes, promises
the best accuracy and repeatability in applications with low to
medium pressure and temperature requirements.
Plant uptime is increased with the maintenance-free
design
The Annubar sensor is designed to prevent wear and blockage in
the pipe. The electronics are the most stable in the industry and
allows up to 10 year calibration cycles, providing significant
maintenance savings.
Energy savings gained through minimal permanent
pressure loss
The non-constricting design of the Annubar sensor creates
minimal blockage in the pipe, which reduces permanent pressure
loss. Permanent pressure loss can be converted directly into
energy savings in the form of compressor cost for gas, electrical
cost for pumping liquids, and fuel costs for generating steam.
Industry leading integrated DP flowmeters
By integrating pressure transmitter electronics with the Annubar,
Rosemount provides the highest performing insertion DP
flowmeter. This fully integrated flowmeter eliminates the need for
instrument fittings, tubing, valves, adapters, manifolds, and
mounting brackets, thereby reducing welding and installation time.
Advanced PlantWeb® Functionality
Rosemount Annubar flowmeters power PlantWeb
through a scalable architecture, advanced
diagnostics, and MultiVariable capabilities. This
reduces operational and maintenance expenditures
while improving throughput and utilities
management.
Rosemount DP Flow Solutions
Annubar Flowmeter Series: Rosemount 3051SFA,
3095MFA, 485, and 285
The state-of-the-art, fifth generation Rosemount 485 Annubar
combined with the 3051S or 3095MV MultiVariable transmitter
creates an accurate, repeatable and dependable insertion-type
flowmeter. The Rosemount 285 provides a commercial product
offering for your general purpose applications.
Compact Orifice Flowmeter Series: Rosemount
3051SFC, 3095MFC, and 405
Compact Orifice Flowmeters can be installed between existing
flanges, up to a Class 600 (PN100) rating. In tight fit applications,
Integral Orifice Flowmeter Series: Rosemount
3051SFP, 3095MFP, and 1195
These integral orifice flowmeters eliminate the inaccuracies that
become more pronounced in small orifice line installations. The
completely assembled, ready to install flowmeters reduce cost and
simplify installation.
Orifice Plate Primary Element Systems: Rosemount
1495 and 1595 Orifice Plates, 1496 Flange Unions and
1497 Meter Sections
A comprehensive offering of orifice plates, flange unions and
meter sections that is easy to specify and order. The 1595
Integral mount head allows close coupling to
most Rosemount transmitters which provides
flowmeter capabilities.
2
a conditioning orifice plate version is available, requiring only two
diameters of straight run upstream.
Conditioning Orifice provides superior performance in tight fit
applications.
Product Data Sheet
00813-0100-4028, Rev CA
March 2008 Rosemount 285 Annubar Primary Element
285 Annubar Primary Element Series Selection Guide
Rosemount 285 Annubar with Pak-Lok Mounting
• Designed to give the highest performance in applications with low to
medium pressure and temperature requirements
• Innovative T-shape design provides accuracy to ±1.00%
• Optional integral manifold head allows direct mounting of DP transmitters
• Ideal fluid type: liquid, gas, and steam
Rosemount 285 Annubar
with Duct Mount (No compression fitting)
• Combines the 285 Annubar technology with duct
mounting installation
• For applications requiring duct mounting installation
• Ideal fluid types: gas
• Threaded stud for opposite side support
Rosemount 285 Annubar with Duct Mount
Compression Fitting
• For application in ducts requiring additional mounting support
• Ideal fluid types: gas
• No opposite side support required
Rosemount 285 Annubar
with Pak-Lok Mounting
Rosemount 285
Annubar with Duct Mount
Rosemount 285
Annubar with Duct Mount
Compression Fitting
3
Product Data Sheet
00813-0100-4028, Rev CA
March 2008Rosemount 285 Annubar Primary Element
Rosemount 285 Annubar Primary
SPECIFICATIONS
Performance
Performance Statement Assumptions
Measured pipe I.D.
Discharge Coefficient Factor
Liquid: ±1.0% of flow rate
Gas and Steam: ±2.0% of flow rate
Repeatability
±0.1%
Line Sizes
• Sensor Size 1: 2-in. to 8-in. (50 to 200 mm)
• Sensor Size 2: 8-in. and above
For larger line sizes, consult factory.
NOTE
Some mounting styles not available in large line
sizes.
TABLE 1. Reynolds Number and Probe Width
Sizing
Contact an Emerson Process Management representative for
assistance. A Configuration Data Sheet is required prior to order
for application verification.
Flow Turndown
10:1or better
Functional
Service
• Liquid
• Gas
• Steam (limited)
Temperature Limits(1)
• -40 to 300°F (-40 to 149°C)
• -40 to 850°F (-40 to 454°C) for Duct Mount Version (D1) only
Pressure Limits(1)
• Pak-Lok: 150# ANSI (275 psig at 100 °F (19 bar at 38 °C))
• Duct Mount (D1 & D2): 10 PSIG (0.6 bar)
Pressure and Temperature Limits
Direct Mount Electronics
• Up to 150# ANSI (275 psig at 100 °F (19 bar at 38 °C))
• Maximum temperature: 500 °F (260 °C)
• Integral temperature measurement is not available.
Remote Mount Electronics
• Up to 150# ANSI (275 psig at 100 °F (19 bar at 38 °C)).
• Integral temperature measurement is not available.
Physical
Annubar Sensor Material
• 316 Stainless Steel
Pak-Lok
See “Dimensional Drawings” on page 6
Pak-Lok Model (option P1)
• Provided with a compression sealing mechanism rated up to
150# ANSI (275 psig at 100 °F (19 bar at 38 °C))
• PTFE Packing (–40 to 300 °F (–40 to 149 °C))
Duct Mount
See “Dimensional Drawings” on page 7.
Duct Mount without Compression Fitting Model (option D1)
• Provided with duct mounting rated up to
10 psig at 850°F (0.6 bar at 454°C).
Duct Mount with Compression Fitting
See “Dimensional Drawings” on page 8.
Duct Mount with Compression Fitting Model (option D2)
• Provided with duct mount compression fitting rated up to
10 psig at 300°F (0.6 bar at 38°C).
Instrument Connections Temperature Ranges
Sensor
Size
Minimum Rod Reynolds
Number (Rd)
Probe Width (d)
(inches)
1 6500 0.590-in. (14.99 mm)
2 12500 1.060-in. (26.92 mm)
Where
d = Probe width (feet)
v = Velocity of fluid (ft/sec)
p = Density of fluid (lbm/ft3)
µ = Viscosity of the fluid (lbm/ft-sec)
Rd
d v× p×
µ
---------------------=
TABLE 2. Minimum / Maximum Temperature Range
Code Description Temperature
G1 Needle Valves, Carbon Steel -40 to 500°F
(-40 to 260°C)
G2 Needle Valves, Stainless Steel -40 to 500°F
(-40 to 260°C)
B1 Ball Valve, Carbon Steel -40 to 300°F
(-40 to 149°C)
B2 Ball Valve, Stainless Steel -40 to 300°F
(-40 to 149°C)
4
(1) Annubar option selections may effect pressure and tem-
perature limitations.
Product Data Sheet
00813-0100-4028, Rev CA
March 2008 Rosemount 285 Annubar Primary Element
Installation Considerations
Drill Hole Size According to Sensor Size
Straight Run Requirements(1)
(1) Consult the factory for instructions regarding use in
Upstream Dimensions
(Pipe Diameters)
D
o
w
n
s
tr
e
a
m
Without
Vanes(2)
With
Vanes(3)
In
Plane
A
Out of
Plane
A A’ C C’ B
1
8
—
10
—
—
8
—
4
—
4
4
4
2
11
—
16
—
—
8
—
4
—
4
4
4
3
23
—
28
—
—
8
—
4
—
4
4
4
4
12
—
12
—
—
8
—
4
—
4
4
4
5
18
—
18
—
—
8
—
4
—
4
4
4
6
30
—
30
—
—
8
—
4
—
4
4
4
Flowmeter Orientation (Recommended)
Gas (Horizontal)
Liquid and Steam (Horizontal)
Gas (Vertical)
Steam (Vertical)
Sensor Size Diameter
1 3/4-in. (19 mm)
2 15/16-in. (34 mm)
3030
120
30° 30°
120°
F
LO
W
360°
Note: Can also be mounted for Gas Vertical up applications.
F
LO
W
360°
In Plane
Out of Plane
5
square or rectangular ducts.
(2) “In Plane A” means the bar is in the same plane as the elbow. “Out
of Plane A” means the bar is perpendicular to the plane of the
upstream elbow.
(3) Use straightening vane to reduce the required straight run length.
Product Data Sheet
00813-0100-4028, Rev CA
March 2008Rosemount 285 Annubar Primary Element
Dimensional Drawings
Pak-Lok Rosemount 285 Annubar Primary(1)
(1) The Pak-Lok Annubar model is available up to 150# ANSI (275 psig at 100 °F (19 bar at 38 °C)).
Front View Side View Top View
A
REMOTE MOUNT HEAD OPTION
1/4-in. NPT
Connection
B
C
TABLE 3. Rosemount 285 Annubar Primary - Pak-Lok
Sensor Size A (Max) B (Max) C (Max)
1 8.50 (215.9) 5.00 (127.0) 9.00 (228.6)
2 11.00 (279.4) 5.00 (127.0) 9.00 (228.6)
Dimensions are in inches (millimeters)
6
Product Data Sheet
00813-0100-4028, Rev CA
March 2008 Rosemount 285 Annubar Primary Element
Dimensional Drawings (continued)
TABLE 4. Rosemount 285 Annubar with Duct Mount
Duct Mount 285 Annubar Primary
Front View Side View Top View
Sensor Size A (Max)
1 7.00 (177.8)
2 9.00 (228.6)
Dimensions are in inches (millimeters)
A
DIRECT MOUNT HEAD OPTION
WITH VALVES
(F2 OPTION)
7
Product Data Sheet
00813-0100-4028, Rev CA
March 2008Rosemount 285 Annubar Primary Element
Dimensional Drawings (continued)
TABLE 5. Duct Mount with Compression Fitting
Duct Mount with Compression Fitting 285 Annubar Primary
Front View Side View Top View
A
DIRECT MOUNT HEAD OPTION
WITH VALVES
(F2 OPTION)
Note
Maximum opposite side stud length is 11/2-in. (38 mm) long.
Sensor Size A (Max)
1 8.50 (215.9)
2 11.00 (279.4)
Dimensions are in inches (millimeters)
8
Product Data Sheet
00813-0100-4028, Rev CA
March 2008 Rosemount 285 Annubar Primary Element
ORDERING INFORMATION
Rosemount 285 Annubar Primary Ordering Information
Model Annubar Primary Element
285 Economy Annubar
Code Fluid Type
L Liquid
G Gas
S Steam
Code Line Size
020 2-in. (50 mm)
025 21/2-in. (63.5 mm)
030 3-in. (80 mm)
035 31/2-in. (89 mm)
040 4-in. (100 mm)
050 5-in. (125 mm)
060 6-in. (150 mm)
080 8-in. (200 mm)
100 10-in. (250 mm)
120 12-in. (300 mm)
140 14-in. (350 mm)
160 16-in. (400 mm)
180 18-in. (450 mm)
200 20-in. (500 mm)
240 24-in. (600 mm)
300 30-in. (750 mm)
360 36-in. (900 mm)
420 42-in. (1066 mm)
480 48-in. (1210 mm)
600 60-in. (1520 mm)
720 72-in. (1820 mm)
780 78-in. (1950 mm)
840 84-in. (2100 mm)
900 90-in. (2250 mm)
960 96-in. (2400 mm)
Code Pipe I.D. Range (Refer to Pipe ID Range Table for Code)
A Range A from the Pipe I.D. table
B Range B from the Pipe I.D. table
C Range C from the Pipe I.D. table
D Range D from the Pipe I.D. table
E Range E from the Pipe I.D. table
Z Non-standard Pipe I.D. Range or Line Sizes greater than 12 inches (sensor size 2) or greater than 8 inches (sensor size 1).
Code Piping Configuration
C Circular
R Rectangular or Square
Code Pipe Material/Mounting Assembly Material
C Carbon Steel
S 316 Stainless Steel
0 No Mounting (Customer Supplied)
Code Annubar Type
P1 Pak-Lok
9
D1 Duct Mount Plate without Compression Fitting
D2 Duct Mount Plate with Compression Fitting
Continued on Next Page
Product Data Sheet
00813-0100-4028, Rev CA
March 2008Rosemount 285 Annubar Primary Element
Code Sensor Material
S 316 Stainless Steel
Code Sensor Size
1 Sensor Size 1
2 Sensor Size 2
Code Electronics Connection Platform
3 Direct-mount
7 Remote-mount NPT Connections
Code Options
Instrument Connections for Remote Mount Option
G1 Needle Valves, CS
G2 Needle Valves, SS
B1 Ball Valves, CS
B2 Ball Valves, SS
Variable Mount Height
VM Variable Mounting Height for Customer Supplied Mounting
Attach To
H1 Attach to Transmitter
Manifold
F2(1) 3-Valve Manifold, SST
Special Inspection(2)
QC1 Visual and Dimensional Inspection w/Cert
QC7 Inspection and Performance Certificate
Material Traceability Certification (1)
Q8 Material Cert per ISO 10474 3.1.B and EN 10204 3.1.B
Special Shipment
Y1 Mounting Hardware Shipped Separately
(1) Applies to 285 Primary Element only. If F2 option is ordered with Electronic Connections Platform Code '3' (Direct Mount), manifold is integral to head. If
F2 is ordered with Code '7' (Remote Mount), the manifold is supplied loose.
(2) Applies to 285 Primary Element Only.
10
Product Data Sheet
00813-0100-4028, Rev CA
March 2008 Rosemount 285 Annubar Primary Element
Pipe I.D. Range Code–measured in inches (millimeters)
See “Rosemount 285 Annubar Primary Ordering Information” on page 9
For pipes with an Inner Diameter (I.D.) Range / Pipe Wall Thickness not found in this table or with a line size greater than 12-in. (300 mm),
choose option code Z and specify the exact pipe dimensions (I.D. and Pipe Wall Thickness) on the “” on page 11. The Emerson process
Management sizing program will determine this code, based on the application piping.
Line Size
Inner Diameter (I.D.) Range
Pipe Wall Thickness
I.D.
Range
CodeNominal
Max.
O.D.
Option
Code ANSI Pipes Non-ANSI Pipes
S
e
n
s
o
r
S
iz
e
1
2-in.
(50 mm)
2.625-in.
(66.68 mm)
020
1.784 to 1.841-in. (45.31 to 46.76 mm)
0.065 to 0.545-in.
(1.7 to 13.8 mm)
0.065 to 0.488-in. (1.7 to 12.4 mm) A
1.842 to 1.938-in. (46.79 to 49.23 mm) 0.065 to 0.449-in. (1.7 to 11.4 mm) B
1.939 to 2.067-in. (49.25 to 52.50 mm) 0.065 to 0.417-in. (1.7 to 10.6 mm) C
2.068 to 2.206-in. (52.53 to 56.03 mm) 0.065 to 0.407-in. (1.7 to 10.3 mm) D
21/2-in.
(63.5 mm)
3.188-in.
(80.98 mm)
025
2.207 to 2.322-in. (56.06 to 58.98 mm)
0.083 to 0.563-in.
(2.1 to 14.3 mm)
0.083 to 0.448-in. (2.1 to 11.4 mm) B
2.323 to 2.469-in. (59.00 to 62.71 mm) 0.083 to 0.417-in. (2.1 to 10.6 mm) C
2.470 to 2.598-in. (62.74 to 65.99 mm) 0.083 to 0.435-in. (2.1 to 11.0 mm) D
2.599 to 2.647-in. (66.01 to 67.23 mm) 0.083 to 0.515-in. (2.1 to 13.1 mm) E
3-in.
(80 mm)
3.75-in.
(95.25 mm)
030
2.648 to 2.751-in. (67.26 to 69.88 mm)
0.083 to 0.563-in.
(2.1 to 14.3 mm)
0.083 to 0.460-in. (2.1 to 11.7 mm) A
2.752 to 2.899-in. (69.90 to 73.63 mm) 0.083 to 0.416-in. (2.1 to 10.6 mm) B
2.900 to 3.068-in. (73.66 to 77.93 mm) 0.083 to 0.395-in. (2.1 to 10.0 mm) C
3.069 to 3.228-in. (77.95 to 81.99 mm) 0.083 to 0.404-in (2.1 to 10.3 mm) D
31/2-in.
(89 mm)
4.25-in.
(107.95 mm)
035
3.229 to 3.333-in. (82.02 to 84.66 mm)
0.120 to 0.600-in.
(3.0 to 15.2 mm)
0.120 to 0.496-in. (3.0 to 12.6 mm) B
3.334 to 3.548-in. (84.68 to 90.12 mm) 0.120 to 0.386-in. (3.0 to 9.8 mm) C
3.549 to 3.734-in. (90.14 to 94.84 mm) 0.120 to 0.415-in. (3.0 to 10.5 mm) D
4-in.
(100 mm)
5.032-in.
(127.81 mm)
040
3.735 to 3.825-in. (94.87 to 97.16 mm)
0.120 to 0.600-in.
(3.0 to 15.2 mm)
0.120 to 0.510-in. (3.0 to 13.0 mm) B
3.826 to 4.026-in. (97.18 to 102.26 mm) 0.120 to 0.400-in. (3.0 to 10.2 mm) C
4.027 to 4.237-in. (102.29 to 107.62 mm) 0.120 to 0.390-in. (3.0 to 9.9 mm) D
4.238 to 4.437-in. (107.65 to 112.70 mm) 0.120 to 0.401-in. (3.0 to 10.2 mm) E
5-in.
(125 mm)
6.094-in.
(154.79 mm)
050
4.438 to 4.571-in. (112.73 to 116.10 mm)
0.134 to 0.614-in.
(3.4 to 15.6 mm)
0.134 to 0.481-in. (3.4 to 12.2 mm) A
4.572 to 4.812-in. (116.13 to 122.22 mm) 0.134 to 0.374-in. (3.4 to 9.5 mm) B
4.813 to 5.047-in. (122.25 to 128.19 mm) 0.134 to 0.380-in. (3.4 to 9.7 mm) C
5.048 to 5.249-in. (128.22 to 133.32 mm) 0.134 to 0.413-in. (3.4 to 10.5 mm) D
6-in.
(150 mm)
6.93-in.
(176.02 mm)
060
5.250 to 5.472-in. (133.35 to 138.99 mm)
0.134 to 0.614-in.
(3.4 to 15.6 mm)
0.134 to 0.392-in. (3.4 to 9.9 mm) A
5.473 to 5.760-in. (139.01 to 146.30 mm) 0.134 to 0.327-in. (3.4 to 8.3 mm) B
5.761 to 6.065-in. (146.33 to 154.05 mm) 0.134 to 0.310-in. (3.4 to 7.9 mm) C
6.066 to 6.383-in. (154.08 to 162.13 mm) 0.134 to 0.297-in. (3.4 to 7.5 mm) D
8-in.
(200 mm)
9.688-in.
(246.08 mm)
080
7.393 to 7.624-in. (187.78 to 193.65 mm)
0.250 to 0.73-in.
(6.4 to 18.5 mm)
0.250 to 0.499-in. (6.4 to 12.6 mm) B
7.625 to 7.981-in. (193.68 to 202.72 mm) 0.250 to 0.374-in. (6.4 to 9.5 mm) C
7.982 to 8.400-in. (202.74 to 213.36 mm) 0.250 to 0.312-in. (6.4 to 7.9 mm) D
8.401 to 8.766-in. (213.39 to 222.66 mm) 0.250 to 0.364-in. (6.4 to 9.2 mm) E
S
e
n
s
o
r
S
iz
e
2
8-in.
(200 mm)
9.688-in.
(246.08 mm)
080
7.393 to 7.624-in. (187.78 to 193.65 mm)
0.250 to 1.47-in.
(6.4 to 37.3 mm)
0.250 to 1.239-in. (6.4 to 31.4 mm) B
7.625 to 7.981-in. (193.68 to 202.72 mm) 0.250 to 1.114-in. (6.4 to 28.3 mm) C
7.982 to 8.400-in. (202.74 to 213.36 mm) 0.250 to 1.052-in. (6.4 to 26.7 mm) D
8.401 to 8.766-in. (213.39 to 222.66 mm) 0.250 to 1.104-in. (6.4 to 28.0 mm) E
10-in.
(250 mm)
11.75-in.
(298.45 mm)
100
8.767 to 9.172-in. (222.68 to 232.97 mm)
0.250 to 1.470-in.
(6.4 to 37.3 mm)
0.250 to 1.065-in. (6.4 to 27.1 mm) A
9.173 to 9.561-in. (232.99 to 242.85 mm) 0.250 to 1.082-in. (6.4 to 27.5 mm) B
9.562 to 10.020-in. (242.87 to 254.51 mm) 0.250 to 1.012-in. (6.4 to 25.7 mm) C
10.021 to 10.546-in. (254.53 to 267.87 mm) 0.250 to 0.945-in. (6.4 to 24.0 mm) D
10.547 to 10.999-in. (267.89 to 279.37 mm) 0.250 to 1.018-in. (6.4 to 25.9 mm) E
12-in.
(300 mm)
13.0375-in.
(331.15 mm)
120
11.000 to 11.373-in. (279.40 to 288.87 mm)
0.250 to 1.470-in.
(6.4 to 37.3 mm)
0.250 to 1.097-in. (6.4 to 27.9 mm) B
11.374 to 11.938-in. (288.90 to 303.23 mm) 0.250 to 0.906-in. (6.4 to 23.0 mm) C
11.939 to 12.250-in. (303.25 to 311.15 mm) 0.250 to 1.159-in. (6.4 to 29.4 mm) D
11
Product Data Sheet
00813-0100-4028, Rev CA
March 2008Rosemount 285 Annubar Primary Element
Configuration Data Sheet (CDS)
DP FLOW CDS
Complete this form to define a custom flow configuration for DP Flowmeters. Unless specified, the flowmeter will
be shipped with the default values identified by the H symbol.
For technical assistance in filling out this CDS, call a Rosemount representative.
NOTE
Any missing information will be processed with the indicated default values.
* = Required Item
★ = Default
Customer Information
Customer: Contact Name:
Customer Phone: Customer Fax:
Customer Approval Sign-Off: Customer PO:
Calculation Approval
❑ Check this box if a calculation for approval prior to manufacturing is required
Application and Configuration Data Sheet (Required with Order)
Tag:
Model No (1)
* Select fluid type ❑ Liquid ❑ Gas ❑ Steam
* Fluid name(2)
Flowmeter Information (optional)
* Failure Mode Alarm Direction (select one) ❑ Alarm High★ ❑ Alarm Low
Software Tag: ___ ___ ___ ___ ___ ___ ___ ___ (8 characters)
Descriptor: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___