通力3000故障代码(Kone 3000 fault code)

2017-10-14 15页 doc 39KB 31阅读

用户头像

is_650122

暂无简介

举报
通力3000故障代码(Kone 3000 fault code)通力3000故障代码(Kone 3000 fault code) 通力3000故障代码(Kone 3000 fault code) Kone 3000 fault code Code Fault name Reason Operate Recover Test 0001 Long drive time The position signal 30/B30 does not change after a period of running time. Immediate stop Turn off th...
通力3000故障代码(Kone 3000 fault code)
通力3000故障代码(Kone 3000 fault code) 通力3000故障代码(Kone 3000 fault code) Kone 3000 fault code Code Fault name Reason Operate Recover Test 0001 Long drive time The position signal 30/B30 does not change after a period of running time. Immediate stop Turn off the electricity Slow the elevator stopped under 77:U, unplug the 0.61:U/N, to express 0004 Three consecutive simultaneous failures 3 consecutive simultaneous operation, can not receive the correct 77:U/N, 61U/N, 30 signals After 3 failures, stop at the terminal Turn off the electricity - 0007 The gate signal 30/B30 is jammed After starting a period of time, the falling edge of the 30/B30 signal is not detected, and the gate signal 30/B30 is always valid Run to the goal floor and open the door Power off or repair The 30 (B30) signal on the shorted LCECCB (XB24), the lowest pin of the -XB21 0008 NVRAM damage or capacity is not enough When power is transmitted, the capacity of NVRAM is not enough - change the NVRAM - 0014 The gate area monitoring circuit is not released Any one of the 486443:1443:2 has no pull in 2 consecutive runs Run to destination layer out of service Turn off the electricity Runtime makes 443:2 (LCEADO) not pull in 0015 The gate monitoring circuit is not attracted Any one of the 486443:1443:2 is not released in 2 consecutive runs The runtime keeps 443:2 (LCEADO) in hold 0021 The safety loop is blocked Safety loop input 1 no voltage Immediate stop Safety loop connection Disconnect the safety circuit 0022 The running well lock is disconnected Safety loop input 3 no voltage Immediate stop Lock on hoistway door Use the key to open the hall door or unplug the LCE230 XH2 0023 The door lock is broken at the time of operation Safety loop input 2 no voltage Immediate stop Car door lock - 0025 Boot enable fault When the elevator stops, the main contactor is not released Not started Main contactor release Keep 201:1 or 201:2 or 204 all the time 0026 The drive system is out of order The drive system detected a fault (V3F, OK, lights are not lit) Not started Power off or repair Unplug the V3F16es thermal switch or speedometer 0039 The buffer test button is jammed LCECPU board on the buffer test button (buffer test) card dead Not started Until the button is released The elevator catches the button when it starts 0042 Car lighting supervision The car is out of lights Run to destination layer out of service Recovery of car lighting Turn off the 262 light switch 0044 Shutdown fault Try to close the door more often, but the door won't work yet Don't open the door after 5 failures A new call or service Unplug LCE230's XH2 0048 The door opening device continues to work The reverse door signal is valid for more than one minute Keep the door open until the door signal disappears Until the signal disappears LCECCB pulled out the screen connecting line 90 or B90 0051 Boot failure The 5 attempt failed because the hall door was not closed Open the door and try again 5 times A new call or service Unplug LCE230's XH2 0052 The up and down synchronous switches are effective simultaneously 77:U and 77:N are active at the same time Stop now, only RDF can turn on the ladder One of them is effective Unplug 77:U and 77:N on LCECCB 0058 No run timeout There are running requirements, but the elevator does not run more than 100 seconds Try to run automatically every 10 seconds Automatic recovery - 0060 The V3F16 pickup signal is lost No pickup signals are received from the drive system Run to end station Automatic recovery at end station - 0062 Signal loss in gate area After several floors of 61:U/N, the rising edge of the 30/B3 signal is not received Run to the destination layer and not open the door Power off or repair Remove 30 magnets or remove XB21 (30) or XB24 (B3) on LCECCB 0072 The 61:U signal stuck The 61:U signal is not released after leaving the gate area for a period of time Run to destination layer, out of service The XB22 (61:U) on the short line LCECCB has the lowest two pins 0073 61:N signal loss The rising edge of the 61:N signal is not received through the gate layers Unplug XB23 from LCECCB (61:N) 0074 The 61:N signal stuck The 61:N signal is not released after leaving the gate area for a period of time The XB23 (61:N) on the short line LCECCB has the lowest two pins 0075 61:U signal loss The rising edge of the 61:U signal is not received through the gate layers Remove XB22 (61:U) from LCECCB 0076 Gate area surveillance not released for the first time 486443:1443:2 any one running does not attract (ADO/ACL) Run to the destination floor as usual Automatically return to the bottom after 15 seconds Do not pull the 443:2RU contactor 0077 Open door limit fault (has been invalid) The door is open, but the door is not in place Keep the door open for 15 seconds, then close Automatic recovery - 0078 The call button in the car is jammed Any summons within a car cannot be removed for more than 60 seconds Cancel the button's service until the call button returns to normal The call button returns to normal - 0079 Summon button outside the hall Any calling button outside the hall cannot be removed for more than 60 seconds Cancel this button until the call button returns to normal The call button returns to normal - 0082 Gate area supervision is not allowed for the first time 486443:1443:2 any runtime is not released (ADO/ACL) Run to the destination floor as usual Automatically return to the bottom after 15 seconds Keep the 443:2 contactor in hold 0083 Location missing Location does not agree with well signal Run to end station Synchronous position at end station - 0084 Open door limit fault (always valid) The door is closed, but the door is not received - automatic recovery - 0089 DOM supervision Open the hall door (not in the car seat) Run to destination layer out of service Power off or repair Disconnect the DOM CS input 0145 EBD device corrupted - EBD device - 0146 EBD battery damage - EBD batteries - Drive fault Code Drive fault Reason Recover 0101 Drive stop The elevator stopped because the drive system had detected trouble Check other drive faults 0102 Motor overcurrent Drive parameter error / car / counterweight / Runner friction is too big - 0103 Braking resistor The brake resistor is damaged or wired to disconnect the /385, the A2 board is broken Check the brake resistance 0104 Motor overheating Motor temperature is too high or motor is hot, each resistance line is loose - 0105 AC power supply The intermediate DC voltage is too low or too high Maintenance of three-phase power supply voltage and connection 0106 V3F no, OK Braking resistance monitoring motor temperature monitoring, starting fault times out of limits - 0107 Weighing device fault The voltage of the weighing signal is wrong (<0.6V) Weighing device 0108 Motor /Tocho error Tocho polarity reverse, car and counterweight are bad, weighing is not allowed, brake is not opened, drive parameters are not correct overspeed - 0109 Location missing Loss of drive system location Overhaul 77U/N, 61U/N 0110 heatsink OT The radiator after the drive module is overheated - Drive faults in the Setup process 0111 The flying plate 61:N is under 61:U 61:N/U swap Check the order of the 61:N/U 0112 61:U/N overlap too little Check the location of the 61:N/U 0113 Synchronous switch error 77:S fault Check 77:S 0114 The floor distance is too short The distance between two floors is too short Check the position of the magnet 0115 Scale error - 0116 Attic count error Setup unsuccessful or incomplete Do Setup once Network fault Code Network fault Reason Operate Recover One thousand one hundred and one LECCB fault The circuit board is damaged, the connection is wrong or the electricity is out of order Normal deceleration, stop, maintenance, closed Until contact again 1201/2201 The first block of LCECEB fault The circuit board is damaged, the connection is wrong or the electricity is out of order Single ladder continues normal service Until contact again 1202/2202 Second pieces of LCECEB fault Ditto Ditto Ditto 1203/2203 Third pieces of LCECEB fault Ditto Ditto Ditto 1301/2301 LCECOB fault The circuit board is damaged, the connection is wrong or the electricity is out of order Reach the target floor and open the door Until contact again 1401/2401 The first block of LCEFCB fault Network node missing, or node type error, rollcall chain interrupt Continuing normal service Roll call signal detection through 14xx/24xx Block LCEFCB XX fault Ditto Ditto Ditto 1501/2501 The first block of LCEFOB fault Network node missing, or node type error, rollcall chain interrupt Continuing normal service Roll call signal detection through 15xx/25xx Block LCEFOB XX fault Ditto Ditto Ditto One thousand six hundred and one LCEGTW fault The circuit board is damaged, the connection is wrong or the electricity is out of order Single ladder continues normal service Until contact again 1701/2701 The first block of LCEOPT fault The circuit board is damaged, the connection is wrong or the electricity is out of order Single ladder continues normal service Until contact again 17xx/17xx Block LCEOPT XX fault Ditto Ditto Ditto
/
本文档为【通力3000故障代码(Kone 3000 fault code)】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑, 图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。 本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。 网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。

历史搜索

    清空历史搜索